CUMMINS 300KW Natural Gas Generator Set

CUMMINS 300KW Natural Gas Generator Set from China
CUMMINS 300KW Natural Gas Generator Set

Engine of CUMMINS EG300 Natural Gas Generator Set 

Engine Model CUMMINS KT19
Type 6 cylinders in line
Bore * Stroke (mm) 159*159
Displacement(L) 18.9
Compression ratio 9.5:1
Rated speed(rpm) 1500/1800
Inlet type Naturally aspirated
Cooling type Cooling water tank
Fuel System Low and high pressure
ESC Type Special for U.S. GAC natural gas
Ignition sequence 1-5-3-6-2-4
The allowed maximum speed (Natural gas supply closed at this time) 2160 rpm
The allowed maximum rotating speed (The ignition system shut down at this time) 2160 rpm
Oil Capacity 50 L
Cooling water capacity 132 L
Maximum engine back pressure 10.2 kpa
Gas consumption(m3∕kw·h) <0.3
Rough oil consumption(g/kWh) <1.6
Radiator and oil cooler heat 100 KW
Exhaust pipe heat radiation 114 KW
Engine thermal radiation 15 KW
Alternator thermal radiation 6 KW
Cooling water temperature 95 Deg C
Oil temperature <120 Deg C
Exhaust pipe heat energy (above 120 º C section) 280 KW
Exhaust temperature (before vortex ) 650±15 Deg C
Exhaust Flow 3000 m³/h
Fan exhaust flow 13.7 m³/s
Noise level from 1 m  <100 db(A)
   

Alternator of CUMMINS EG300 Natural Gas Generator Set 

Alternator Model Engga EG315M-300N
Excitation Method Brushless Permanent Magnet
Winding pitch 2/3 pitch
Number of poles 4
Bearing number 1
Stator Windings 12 ends
Insulation Class H class
Protection class IP 21 or IP 23
Load type Continuous operation
AVR Model WT-2
Alignment Fly wheel
Temperature Range Less than 125 degrees Celsius
Overload  Capacity- the percentage of rated power 110%
Waveform distortion rate, no-load <5%
Voltage Regulation Mode AVR
Voltage Regulation Range ±5%
Steady State Voltage Regulation ±1%
No-load line voltage sine wave distortion ±2%
Telephone interference factor (TIF) < 50
   

CUMMINS EG300 Natural Gas Generator Set 

Rated Output(KW) 300
Standby Output(KW) 330
Voltage(V) 400
Current(A) 541
Size(mm) 3440*1300*1950
Approximate weight(KG) 4000
Emission levels (Nox) Euro II emission (mg/m³)
Naturally aspirated engine intake air temperature Not more than 45 Deg C
Air temperature before entering the air to air intercooler   82-87(Deg C)
Air temperature after entering the air to air intercooler   35-42(Deg C)
Rated Power @ 0.8 power factor (w / pump s and w / o fan) 300KW (continuous operation)
Total energy input (100% load) 830(KW)
Electrical efficiency 36.20%
Thermal efficiency 87.90%
Control panel(Deepsea or others) Synchronizing Control, Multilingual Mode Digital Control, Diagnostic Function, Direct Text Indicate of Faults, MOBUS Communication Protocol, Compatible Communication, Exchange Telecommunications,  Wired Control Data Output, Automatic or manual start

 Welcome to contact us for more information of  CUMMINS 300KW Natural Gas Generator Set .